RTD Resistance Splitter-Isolator PTi1000_DH/SH/XD

How to read single RTD sensor on two systems? This is how:

the PTi splitter-isolator is used in temperature control systems to split the signal from a single RTD to multiple independent resistance-based measuring systems. Providing full galvanic isolation applied to every port (in/out/power) avoids measurement error due to ground coupled impedance and ensures intrinsic safety separation in explosion risk environments. Special, patented design delivers high accuracy, real-resistance-outputs as RTD sensor-repetition even on pulsed measuring systems, regardless of excitation current or read-pulse duration. Input sensor 4-wire, 3-wire and 2-wire with line-loop compensation connections are supported.

The device is designed for sensor-sharing (i.e. RTD splitter), isolating and conversion between RTDs such as PT100/1000/KTYxx, position detectors, force sensors, etc. For various applications several types are available: Full-Auto-range, several Narrow-range types, RTD + Current & Voltage output; modular – multiple RTD-resistance outputs type and also as Current/Voltage to RTD converter for simulating RTD resistance.

See also: PT 100/1000 Resistance Replicator/Isolator

Features
  • RTD in & RTD Out – resistance output
  • superb accuracy of 0,02% (0,05°C /60°range  for PT100/1000)
  • 2-, 3- & 4-wire connection for input sensor and 2w line loop compensation
  • pulsed (multiplex) measurement compatible
  • conversion between PT100, PT 1000, KTYxx sensors
  • RTD resistance + Current & Voltage out (SH type)
  • RTD simulation & signal from loop extraction (XD type)
  • modular-multiple RTD resistance out (DHf type)
  • OLED / NO-display version
  • intrinsic galvanic separation on every port & Ex option
  • 10–30V AC/DC single power supply

— Related Products —

RTD Current Transmitters

RTD Current Transmitters

Simple to use, but however high-performance RTD-current transmitter RTT150 is available in new…

Mid-Voltage Measurement Transducer

Mid-Voltage Measurement Transducer

Fully insulated measuring transducer is used for floating voltage measurement on mid-voltage AC/DC…

Electrical Charge & Power Meter AHM-400

Electrical Charge & Power Meter AHM-400

AHM-400 electrical charge and power meter is used for AC/DC current, charge and power consumption…

Automatic Mains Polarity Changeover and Main Power Switch LSWR1

Automatic Mains Polarity Changeover and Main Power Switch LSWR1

Wall socket connection usually do not provide any Live – Neutral polarity identification. In some…

Privacy Preference Center